GESTRA Steam Traps & Air Traps

 

         

GESTRA BK Bimetallic Steam Traps

Steam traps with bimetallic regulator up to PN 630/Class 2500. BK steam traps are suited to the toughest operating conditions. 
The bimetallic regulator makes
this steam trap particularlyresistant to waterhammer and frost.

             
         

GESTRA MK/SMK Balanced Pressure Steam Traps

Steam traps with membrane regulator up to PN 40/Class 300. The GESTRA thermostatic capsule exhibits very high control precision
in discharging the condensate.

             
         

GESTRA UNA Ball Float Steam Traps

Steam traps with ball float up to PN 160/Class 900. Especially suitable for condensate discharge without banking-up, for extreme
and sudden fluctuations of pressure and condensate flowrate.

             
         

GESTRA DK Thermodynamic Steam Traps

These steam traps work on the basis of a simple thermodynamic principle. Incoming condensate lifts the disc of the regulator
to the open position, whilst steam causes it to close immediately. The traps in the DK series are simple in construction featuring a small,
compact body and are low in cost.

             
         

GESTRA VKP10 Steam Trap Testing

The VAPOPHONE is used to detect steam leakage in steam systems in order to prevent live steam loss. Live steam leakage is
detected by sound in the ultrasonic range caused by flowing steam. The mechanical ultrasonic vibrations are detected by the sound probe
of the VAPOPHONE and converted into electric signals which are amplified in the measuring instrument and indicated on a meter.

             
         

GESTRA QuickEM Drainage Module Series

QuickEM control drainage modules provide you with all you need to monitor your steam traps. These are pre-assembled units and
include a steam trap, sight glass, check valve, stop valve and bypass pipe plus all the necessary pipes, flanges, gaskets and fasteners.
This packaged unit is quick and easy to install.

             
         

GESTRA GMF manifolds

GESTRA Steam trap manifolds are ideal for steam distribution and condensate collection in plants with large steam trap populations.

             
         

GESTRA Air Traps

The AK 45 rapidly and automatically discharges air and condensate from steam systems on start-up and drains residual fluid
when the system is shut-down.

Benefits:

- To prevent water hammer and frost damage

- Inner parts of corrosion-resistant stainless steel

- Hand-purging knob for removing dirt